Analysis and Calculations in Medium Voltage Electrical Systems833
Abstract
The electrical installation of an industrial site is a complex structure. Analyzing behavior in a transient condition allows optimum selection of the operation and protection devices in the installati... see moreon design phase; in addition, possible weaknesses and critical points can be highlighted in advance, allowing prevention of potential problems, damage to machinery, and costly periods of down time.
In order to completely satisfy the needs and expectations of the customer, in ABB Electrification Business an important role is played by analyses and consulting services offered by Field Application Support (FAS) specialist.
In this session of the "EMTP User conference", representatives from the Italian ABB Distribution Solution division, based in Dalmine (BG), will show how EMTP tool supports the analyses performed within the "Medium Voltage Circuit Breaker Suitability" reports that are provided to customers looking for switching devices for special applications. In particular, the today presentation will focus on "CB suitability" study approach for the Generator Circuit Breaker and the Filter Harmonics switching applications
Tag(s): TRV, generator breaker, filter, switching
Real Case of a Resonance in a Power Plant851
Abstract
Overvoltages were identified on the MV and LV networks of a Hydro Power Plant as the cause of the trip of the LV maximum voltage protection, compromising the normal operation of the system. Following ... see morethis event, measurements were conducted and the presence of a very high 23rd harmonic, potentially responsible for the various overvoltages, was identified associated to the operation of the Plant’s Synchronous Machine Frequency Control System (FCS). It was concluded then that this harmonic would have its origin in the FCS and would be amplified due to a possible resonance in the Power Plant internal network. A digital simulation study, using EMTP, was conducted to identify and characterize the resonance in the system and to propose mitigation solutions. The simulation models were developed using the equipment data and the system characteristics. The models were duly validated with measurements made both in time and frequency domains and it was possible to identify the origin of the overvoltages and their propagation in the system. It was concluded that the resonance occurred between a 30/11 kV Power Transformer and a 30 kV cable with 850 m.
This conclusion was supported by the results obtained in the measurements. Several alternatives were analyzed as mitigation solutions: - Installation of capacitors; - Different bonding techniques of the 30 kV cable sheaths; - Changing the 30 kV cable length; - Installation of a harmonic filter; The advantages and disadvantages of each solution were weighed also considering the ease of implementation, namely the available room. It was concluded that the installation of capacitors would be the best option. Measurements were conducted after the capacitor’s installation confirming the success of this solution.
Tag(s): harmonics, power uality, resonance
Design and Performance Assessment of Harmonic Filters Using EMTP835
Abstract
In order to permit access to a public electricity network, a network operator will impose compliance with certain technical requirements, which must be met by the potential network user seeking the co... see morennection to the network.
These technical requirements are typically quite extensive and detailed and generally include requirements for compliance with power quality standards, including harmonic distortion standards. As a result of the requirement to comply with harmonic distortion standards and the requirements therein, it is sometimes necessary to provide harmonic filtering in order to ensure the public network will remain within the required harmonic distortion limits under all normal operating conditions.
This presentation gives a study case for a connection to a 400kV network which required design and installation of a number of filters in order to ensure compliance with the harmonic distortion limits on the public network.
As part of the assessment and design process, a number of studies was undertaken in order to ensure all aspects of the filter system design perform as required, under all operating conditions. These studies included:
• harmonic propagation and distortion calculations,
• filter configuration and optimisation studies,
• filter loading studies,
• filter transient studies,
• filter protection studies.
The tool used in the assessments was EMTP. The presentation will demonstrate certain aspects of the EMTP capability and use in steady state and electromagnetic transient studies applied to the filter system design, validation and compliance studies.
Tag(s): railway, traction, power quality, harmonics, scripting